SWG-MV-01 · Acceptance · NETA ATS-2025 · AI Generated
Main Substation Commissioning (26-001) · J. Smith, NETA Level III
Conduct safety briefing — review arc-flash analysis per IEEE 1584. Incident energy: 12.4 cal/cm2 (CAT 3). Confirm all personnel have correct arc-rated PPE, face shield, and voltage-rated gloves. Review emergency rescue plan.
Establish LOTO per OSHA 1910.147. De-energize switchgear from upstream source. Lock out utility breaker BKR-MV-UTIL and generator breaker BKR-MV-GEN. Verify zero energy state on all phases using Salisbury voltage detector rated for 15kV. Apply safety grounds on Bus Section 1 and Bus Section 2.
Verify all test instrument calibration certificates are current. Record serial numbers and calibration due dates for: (1) Megger S1-5010 5kV megger, (2) Megger DLRO-200 micro-ohmmeter, (3) Megger DELTA 4110 power factor test set.
Verify switchgear nameplate data matches specification and single-line diagram. Record: manufacturer, voltage class, BIL, continuous current rating, short-circuit withstand rating.
Inspect all 6 switchgear sections for shipping damage, proper alignment, and completeness of installation. Check all covers, barriers, and phase barriers are in place.
Verify all bus bar connections are torqued to manufacturer specification (ABB torque spec: 75 N-m for main bus, 45 N-m for ground bus) using calibrated torque wrench. Apply witness marks after verification.
Rack each breaker (BKR-1 through BKR-6) through all positions: Connected, Test, Disconnected. Verify racking mechanism operates smoothly and position indicators are correct at each position.
Verify all shutters operate correctly on each cubicle. With breaker racked out, confirm shutters fully close. With breaker racked in, confirm shutters open to expose primary disconnect stabs.
Verify arc flash labels are installed on each cubicle per NFPA 70E 130.5(H). Confirm: incident energy, working distance, PPE category, shock hazard boundary.
Perform insulation resistance test on Bus Section 1: Phase A to Ground. Apply 5000V DC using Megger S1-5010 for 1 minute. Record 1-minute IR value. Record ambient temperature for correction per IEEE 43.
Perform insulation resistance test on Bus Section 1: Phase B to Ground. Apply 5000V DC for 1 minute.
Perform insulation resistance test on Bus Section 1: Phase C to Ground. Apply 5000V DC for 1 minute.
Perform insulation resistance test: Phase A to Phase B on Bus Section 1. Apply 5000V DC for 1 minute.
Perform contact resistance test on BKR-1 primary disconnect contacts using DLRO-200 at 100A DC test current. Measure Phase A.
Perform contact resistance test on BKR-1: Phase B.
Perform contact resistance test on BKR-1: Phase C.
Perform power factor test on Bus Section 1 insulation using DELTA 4110. Test each phase-to-ground and phase-to-phase. Temperature-correct results to 20C.