Technician ·

Project Status

Main Substation Commissioning

Dominion Energy·Henrico Data Center — Building A·Project 26-001
64%Complete
On Track3 Tested6 Remaining2 Open Issues

Start Date

2026-03-15

Target Completion

2026-05-30

Equipment Summary

TagDescriptionStatusLast Test
SWG-MV-0115kV Metal-Clad Switchgear — Main BusIn Progress2026-04-10
XFMR-012000 kVA Dry-Type TransformerComplete2026-04-08
XFMR-021500 kVA Dry-Type TransformerComplete2026-04-09
SWG-LV-01480V Low-Voltage SwitchgearPending--
SWG-LV-02480V Low-Voltage Switchgear — EmergencyPending--
ATS-01Automatic Transfer Switch — Normal/EmergencyComplete2026-04-07
PNL-DC-01125VDC Station Battery & ChargerNeeds Attention2026-04-11
GEN-012MW Diesel GeneratorPending--
UPS-01500 kVA UPS SystemPending--
MCC-01Motor Control Center — HVACPending--

Open Issues

1 Critical1 Major1 Minor
DEF-001MajorSWG-MV-01

One section of the main switchgear showed lower-than-expected insulation readings. Requires cleaning and re-testing before the equipment can be energized.

In Repair
DEF-002CriticalPNL-DC-01

Battery cell #14 capacity is below the required minimum. The cell needs to be replaced to ensure reliable backup power.

Open
DEF-003MinorXFMR-01

A minor oil seep was noticed at a gasket connection. The gasket has been tightened; monitoring to confirm the leak has stopped.

Resolved